Not in facts.json. Verbatim: "The minimum required air gap shall be measured vertically from the lowest end of a potable water outlet to the flood rim of the fixture or receptacle into which it discharges and shall be twice the effective opening of the potable water outlet. ii. If the outlet is found to be at a distance that is less than three times the effective opening away from a wall or similar vertical surface; the minimum required air gap shall be three times the effective opening of the outlet. iii. In no case shall the minimum required air gap be less than shown in ... Table 7". Table 7: lavatories (openings not greater than 1/2 in.) 1 inch / 1.50 inches near a wall; sinks, laundry sinks, gooseneck bath faucets (not greater than 3/4 in.) 1.5 / 2.25 inches; over-rim bath fillers (not greater than 1 in.) 2 / 3 inches.
If a spout is submerged, any vacuum in the supply will siphon the fixture's contents back into the drinking water. The surprise from the lab is that even a spout above the water is not automatically safe.
Under a strong enough vacuum, atmospheric pressure can push water up across open air into the outlet. Bureau of Standards researchers measured the 'critical air gap' at which this stops, and found it grows with outlet diameter and grows again when walls sit close to the spout.
Codes therefore give the safe gap as a multiple of diameter, with an absolute minimum, instead of one fixed number.
NBS report BMS 28 by Gene E. Golden and Roy B. Hunter measures critical air gaps.
Source: https://archive.org/details/backflowpreventi28gold
BMS 28 recommends the 2x-diameter rule.
Source: https://archive.org/details/backflowpreventi28gold
Near walls, a larger multiple applies (3x in the report's conclusion 9), and the report recommends a 1-inch minimum.
Source: https://archive.org/details/backflowpreventi28gold
Terminology: the ASA Subcommittee on Air Gaps recommends saying 'backflow connection' instead of 'cross-connection' for plumbing.
Source: https://archive.org/details/backflowpreventi28gold
Mnemonic: 'Twice the hole, never under an inch; near a wall, make it three.' That matches MA (2x the effective opening; 3x when the outlet is within 3 openings of a wall; Table 7 starts at 1 in. for a lavatory). The true image behind it: in a 1939 federal lab, water was pulled up through open air into a faucet under vacuum.
Any space above the water is enough.
Water can jump a small gap under vacuum (BMS 28). The gap must be at least the critical value plus a safety margin.
An air gap never needs inspection.
EPA says air gaps must be inspected as frequently as mechanical backflow preventers, because people extend spouts or add hoses.
Air gap and air break are the same thing.
An air gap protects potable supply outlets. An air break is an indirect-waste arrangement on the drain side, and the rules differ.
What is the minimum air gap for a lavatory faucet?
The gap must be tall enough that, even with the basin filled to its flood rim and the supply under vacuum, water cannot be drawn up into the outlet. A larger opening can pull water across a larger distance, so the gap grows with the outlet size (twice the effective opening), with 1 inch as the floor. A 'whichever is less' rule would let dangerously small gaps pass.
A required air gap at a fixture is measured from the:
The flood level rim is the highest level water can reach before it spills over the fixture, so it is the worst case. Measuring the gap from the supply outlet down to that rim guarantees that even a full, overflowing fixture cannot touch the spout and be siphoned into the supply; measuring to the basin bottom would overstate the protection.
What is the difference between an air gap and an air break in indirect waste piping?
Both leave the waste pipe open to the atmosphere so sewage cannot be siphoned or pushed back into it. An air gap is full separation: even if the receptor floods to its rim, the water cannot reach the pipe. An air break ends below the rim, so a flooded receptor can reach the pipe, which is why it is allowed only where the code permits.