Air Gaps

Code Stories · PressureTest

The rule in Massachusetts today

Not in facts.json. Verbatim: "The minimum required air gap shall be measured vertically from the lowest end of a potable water outlet to the flood rim of the fixture or receptacle into which it discharges and shall be twice the effective opening of the potable water outlet. ii. If the outlet is found to be at a distance that is less than three times the effective opening away from a wall or similar vertical surface; the minimum required air gap shall be three times the effective opening of the outlet. iii. In no case shall the minimum required air gap be less than shown in ... Table 7". Table 7: lavatories (openings not greater than 1/2 in.) 1 inch / 1.50 inches near a wall; sinks, laundry sinks, gooseneck bath faucets (not greater than 3/4 in.) 1.5 / 2.25 inches; over-rim bath fillers (not greater than 1 in.) 2 / 3 inches.

Why it exists

If a spout is submerged, any vacuum in the supply will siphon the fixture's contents back into the drinking water. The surprise from the lab is that even a spout above the water is not automatically safe.

Why it exists (cont.)

Under a strong enough vacuum, atmospheric pressure can push water up across open air into the outlet. Bureau of Standards researchers measured the 'critical air gap' at which this stops, and found it grows with outlet diameter and grows again when walls sit close to the spout.

Why it exists (cont.)

Codes therefore give the safe gap as a multiple of diameter, with an absolute minimum, instead of one fixed number.

1939

NBS report BMS 28 by Gene E. Golden and Roy B. Hunter measures critical air gaps.

Source: https://archive.org/details/backflowpreventi28gold

1939

BMS 28 recommends the 2x-diameter rule.

Source: https://archive.org/details/backflowpreventi28gold

1939

Near walls, a larger multiple applies (3x in the report's conclusion 9), and the report recommends a 1-inch minimum.

Source: https://archive.org/details/backflowpreventi28gold

1939

Terminology: the ASA Subcommittee on Air Gaps recommends saying 'backflow connection' instead of 'cross-connection' for plumbing.

Source: https://archive.org/details/backflowpreventi28gold

Make it stick

Mnemonic: 'Twice the hole, never under an inch; near a wall, make it three.' That matches MA (2x the effective opening; 3x when the outlet is within 3 openings of a wall; Table 7 starts at 1 in. for a lavatory). The true image behind it: in a 1939 federal lab, water was pulled up through open air into a faucet under vacuum.

Myth

Any space above the water is enough.

Reality

Water can jump a small gap under vacuum (BMS 28). The gap must be at least the critical value plus a safety margin.

Myth

An air gap never needs inspection.

Reality

EPA says air gaps must be inspected as frequently as mechanical backflow preventers, because people extend spouts or add hoses.

Myth

Air gap and air break are the same thing.

Reality

An air gap protects potable supply outlets. An air break is an indirect-waste arrangement on the drain side, and the rules differ.

Check 1

What is the minimum air gap for a lavatory faucet?

  1. 1 inch or twice the outlet diameter, whichever is greater
  2. 1/2 inch or the outlet diameter, whichever is greater
  3. 3 inches or three times the outlet diameter, whichever is less
  4. 1 inch or 1.5 times the outlet diameter, whichever is less

The gap must be tall enough that, even with the basin filled to its flood rim and the supply under vacuum, water cannot be drawn up into the outlet. A larger opening can pull water across a larger distance, so the gap grows with the outlet size (twice the effective opening), with 1 inch as the floor. A 'whichever is less' rule would let dangerously small gaps pass.

Check 2

A required air gap at a fixture is measured from the:

  1. Supply outlet (spout) to the flood level rim
  2. Faucet handle to the drain outlet of the basin
  3. Trap weir to the finished floor below
  4. Spout outlet to the bottom of the basin

The flood level rim is the highest level water can reach before it spills over the fixture, so it is the worst case. Measuring the gap from the supply outlet down to that rim guarantees that even a full, overflowing fixture cannot touch the spout and be siphoned into the supply; measuring to the basin bottom would overstate the protection.

Check 3

What is the difference between an air gap and an air break in indirect waste piping?

  1. Air gap: outlet above the flood rim. Air break: outlet below the rim, above the trap seal.
  2. Air gap: outlet below the flood rim. Air break: outlet above the rim and the trap seal.
  3. Air gap: used only on water supply lines. Air break: used only on indirect waste lines.
  4. Air gap: outlet sealed tight to the receptor. Air break: outlet left open to the room air.

Both leave the waste pipe open to the atmosphere so sewage cannot be siphoned or pushed back into it. An air gap is full separation: even if the receptor floods to its rim, the water cannot reach the pipe. An air break ends below the rim, so a flooded receptor can reach the pipe, which is why it is allowed only where the code permits.