Grease Interceptors (FOG)

Code Stories · PressureTest

The rule in Massachusetts today

Not in facts.json. Verbatim, 10.09(1)(b)2.f: "Interceptors shall be located not more than 25 feet of the most remote fixture being served." 5: "Interceptors shall have a capacity of not less than two pounds of grease for each gallon-per-minute (GPM) of flow." 2.b: "A vent shall be installed downstream of all interceptors". 3.b: "The waste discharge from a commercial food waste disposer shall not discharge into the sanitary drainage system through an interceptor."

Why it exists

Grease goes down the drain as a hot liquid, cools in the pipe, and solidifies, sticking to the walls and building up until the sewer backs up or overflows. EPA's report to Congress found grease was the most common cause (47%) of reported sewer blockages.

Why it exists (cont.)

An interceptor slows the flow and gives it time to cool, so grease, which is lighter than water, floats and is held back while the clearer water leaves. Federal pretreatment rules also bar discharges of 'solid or viscous pollutants in amounts which will cause obstruction' in the public sewer.

1884

Nathaniel T. Whiting of San Francisco patents a grease trap (US 306,981, Oct. 21, 1884).

Source: https://patents.google.com/patent/US306981

1940

BMS 66 leaves grease interceptors to local authority, and allows an interceptor plus a fixture trap if a vent intervenes.

Source: https://archive.org/stream/plumbingmanual66subc/plumbingmanual66subc_djvu.txt

2004

EPA Report to Congress on CSOs and SSOs (EPA-833-R-04-001), as quoted in EPA's 2012 food-service fact sheet.

Source: https://www.hampton.gov/DocumentCenter/View/50257/EPA-pretreatment-food-service-PDF

2012

EPA fact sheet (EPA-833-F-12-003) citing the pretreatment prohibition at 40 CFR 403.5(b)(3).

Source: https://www.hampton.gov/DocumentCenter/View/50257/EPA-pretreatment-food-service-PDF

Make it stick

Mnemonic: 'Hot down the drain, hard in the main.' Grease is liquid in the sink and solid in the sewer, so the interceptor has to catch it in between.

Myth

Hot water and dish soap flush grease safely away.

Reality

They only move it downstream, where it cools and solidifies. EPA's point is that grease 'solidifies, reduces conveyance capacity, and blocks flow.'

Myth

An interceptor is a second fixture trap, so it's prohibited double trapping.

Reality

In 1940 BMS 66 allowed an interceptor in addition to a fixture trap if a vent was between them. MA today says interceptors 'shall not be considered traps unless they meet' the 2-to-4-inch seal rule (10.09(1)(b)1.a), and 'a vent shall be installed downstream of all interceptors' (10.09(1)(b)2.b).

Check 1

A grease interceptor (grease trap) is required for:

  1. Residential kitchen sinks, including those with food waste grinders
  2. All floor drains located in any commercial building
  3. Commercial laundry fixtures that discharge lint-laden waste
  4. Commercial kitchen fixtures discharging grease-laden waste

Fats, oils and grease flow as liquids when hot but congeal as they cool in the building drain and public sewer, forming blockages. A grease interceptor slows and cools the flow so grease separates and is held back before it leaves the building; commercial kitchens produce that load continuously, while laundries need lint interceptors, not grease interceptors.

Check 2

A grease interceptor is rated at 25 GPM flow-through. What minimum grease retention capacity does 248 CMR require?

  1. 25 pounds
  2. 12.5 pounds
  3. 100 pounds
  4. 50 pounds

Interceptors must hold not less than 2 pounds of grease for each GPM of flow: 25 GPM x 2 lb/GPM = 50 lb. Table 2 in 10.09 lists the same 25 GPM = 50 lb pairing.

Check 3

An inside grease interceptor must be located not more than how far from the most remote fixture it serves?

  1. 10 feet
  2. 15 feet
  3. 50 feet
  4. 25 feet

248 CMR requires interceptors within 25 feet of the most remote fixture served, so grease does not congeal in a long branch before reaching it. If an exterior interceptor is within 25 feet of the most remote fixture, no inside interceptor is needed.

Now practice it

pressuretest.me/learn/grease-interceptors/