Venting: Why Vents Exist

Code Stories · PressureTest

The rule in Massachusetts today

Verbatim, 248 CMR 10.08(2)(e): vents shall be installed "so that at no time shall the trap be subjected to a pressure differential of more than one inch of water." 10.16(1)(d): "The vent pipe opening from a soil or waste pipe, except for water closets and similar fixtures shall not be below the weir of the trap." 10.16(1)(e): "Automatic vents and air admittance valves are not permitted without Special-Permission from the Board."

No vent within two pipe diameters of the trap weir (248 CMR 10.16(1)(b))

Vent at least 1-1/4 in. and at least half the drain served (248 CMR 10.16(11)(a))

Minimum vent stack 3 in. (248 CMR 10.16(2)(a))

Vent extends between 18 and 24 inches above the roof penetration (248 CMR 10.16(3)(a)1)

Vent extends between 18 and 24 inches above the roof penetration (248 CMR 10.16(3)(a)1)

Non-floor-mounted fixtures: vent rises vertically or at 45 deg to at least 6 in. above flood-level rim before offsetting horizontally (248 CMR 10.16(4)(b)1.b)

Why it exists

Water falling down a stack acts like a loose piston. It leaves low pressure behind it, which can siphon traps, and pushes air ahead of it, which can blow seals out as back pressure.

Why it exists (cont.)

A single fixture can also empty its own trap (self-siphonage) when its discharge fills the trap arm and pulls the seal along behind it. A vent gives air another way in or out, so the pressure swing is relieved through the vent instead of through the water seal.

Why it exists (cont.)

The 1940 federal manual defines a vent in exactly these terms: a pipe to provide air 'to protect trap seals from siphonage and back pressure.'

1883

Boston architect J. Pickering Putnam begins his trap-siphonage experiments for the Boston Board of Health.

Source: https://en.wikisource.org/wiki/Popular_Science_Monthly/Volume_33/July_1888/Safety_in_House-Drainage

1888

Back-venting was already standard, and critics pointed out a side effect: moving air over the seal evaporates it.

Source: https://en.wikisource.org/wiki/Popular_Science_Monthly/Volume_33/July_1888/Safety_in_House-Drainage

1888

Hoyt credits a Massachusetts sanitarian with building the scientific basis of house drainage.

Source: https://en.wikisource.org/wiki/Popular_Science_Monthly/Volume_33/July_1888/Safety_in_House-Drainage

1940

BMS 66 defines a vent by what it does.

Source: https://archive.org/stream/plumbingmanual66subc/plumbingmanual66subc_djvu.txt

1940

BMS 66 defines the back vent.

Source: https://archive.org/stream/plumbingmanual66subc/plumbingmanual66subc_djvu.txt

Make it stick

Mnemonic (true physics): a juice can with one hole glugs, because air and liquid are fighting over the same opening. Punch a second hole and it pours smoothly. The vent is the second hole: it lets air in so your trap water doesn't get pulled out to fill the gap.

Myth

Vents exist to let the smell out of the house.

Reality

Their primary job is controlling pressure to protect trap seals. Releasing gas above the roof is secondary.

Myth

A bigger drain pipe removes the need for venting.

Reality

Oversizing reduces some pressure swings but does not stop self-siphonage or stack-induced pressures. Codes size and place vents on their own terms.

Myth

Venting is 'modern'.

Reality

Venting and the argument over how much of it is needed date to the 1880s (Hoyt 1888, Putnam 1883).

Check 1

What is the primary purpose of a plumbing vent system?

  1. To equalize pressure and prevent trap siphonage
  2. To carry excess water from fixtures to the building drain
  3. To circulate hot water back to the water heater loop
  4. To connect roof leaders and area drains to the storm drain

Water falling through a drain pushes air ahead of it and leaves a vacuum behind it. Without air let in through vents, those pressure swings would blow out or siphon trap seals and let sewer gas into the building. Vents carry air, not water, which rules out the drainage choices.

Check 2

A vent connection must be at least how far from the trap weir (to avoid crown venting)?

  1. One pipe diameter
  2. Four pipe diameters
  3. Two pipe diameters
  4. Six pipe diameters

The crown of a trap's outlet is where water pouring over the weir strikes hardest. A vent opening there is hit by the flow, collects solids and scale and eventually closes, so the vent must connect at least two pipe diameters downstream of the weir, above the flow path.

Check 3

An individual vent must be at least one-half the diameter of the drain served, but never smaller than:

  1. 1 inch
  2. 1-1/2 inches
  3. 1-1/4 inches
  4. 2 inches

A vent must be big enough to move the air that flowing water displaces. Tying it to half the drain diameter scales it with the load, and the 1-1/4 in. floor keeps very small vents from being choked by debris or condensate. 1-1/2 in. is the tempting wrong answer because it is the vent size for a 3 in. drain.

Now practice it