Drainage Fixture Units (DFU): Hunter's Probability Method

The rule in Massachusetts today

Water closet, tank type = 4 DFU; water closet, valve operated = 6 DFU; lavatory = 1; horizontal fixture branch 2 in. = 6 DFU max; 3 in. = 34 DFU, not more than four water closets (facts.json, verified against 248 CMR 10.15).

248 CMR 10.15 Table 1 (DFU values), Table 2 (horizontal drains), Table 3 (stacks); 10.15(2)(b) · confirm in the current 248 CMR

Why it exists

No building runs every fixture at once, and sizing pipes as if it did wastes money. Sizing for the average load would fail at peak times. Roy B. Hunter at the National Bureau of Standards treated fixture use as a probability problem: given how long each fixture flows and how often it is used, how many are likely to be flowing at the same moment? He weighted fixtures on an 'arbitrary scale' (fixture units) and designed for a load that would be exceeded only a small fraction of the time. His worked example gave 'wholly satisfactory service 99 percent of the time.' Because the method is statistical, doubling the number of fixtures does not double the design load. That is why fixture-unit totals do not convert linearly to flow.

How it came to be

  1. 1924 — Hunter's own reference [1] is the Commerce Department's earlier plumbing requirements, the base his work built on. archive.org
  2. 1936 — Hunter cites MIT's Thomas R. Camp on water-closet hydraulics, published by the Massachusetts State Association of Master Plumbers. archive.org
  3. 1940 — BMS 65 defines the fixture unit. archive.org
  4. 1940 — Hunter's design criterion. archive.org
  5. 1940 — Hunter is explicit that the method estimates a probability, not a maximum. archive.org
  6. 1940 — For drainage, Hunter gives the water closet the same weight whether it has a flush valve or a tank. archive.org
  7. 1940 — Report issued; NIST catalogs it as NBS BMS 65, dated 1940. nist.gov

Make it stick

Mnemonic: 'A fixture unit is a vote, not a volume.' Each fixture gets a weighted vote on how big the pipe must be, and the table turns the total votes into a size.

On the exam

Expect MA table lookups (248 CMR 10.15 Table 1: tank WC 4, valve WC 6, lavatory 1, tub 2, residential shower 2, residential kitchen sink 2, laundry connection 3), maximum DFU per pipe size and slope (Table 2 horizontal: 1-1/2 in. 3, 2 in. 6, 3 in. 34 with no more than four water closets, 4 in. 160; Table 3 stacks), adding DFUs for a bathroom group, and the idea that DFU totals are not additive flows. Continuous flows count 2 fixture units per gpm (10.15(2)(b)). WSFU (water supply) and DFU (drainage) are separate tables.

What people get wrong

Try it: 3 real practice questions

Q1. Under 248 CMR 10.15 Table 1, what is the drainage fixture unit value of a tank-type toilet?

Q2. Using 248 CMR 10.15 Table 1, what is the total DFU load of a tank-type toilet, a lavatory (1-1/4" outlet) and a bathtub?

Q3. What is the maximum number of fixture units (DFU) allowed on a 2-inch horizontal branch?

These come from the PressureTest bank. Start 7 days free for the full bank, timed exam simulations and drawn isometric problems.