The rule in Massachusetts today

Not in facts.json (only pex-wh relates). Verbatim, 10.14(6)(f)2: "All storage water heating equipment capable of heating water in excess of 212°F shall be equipped with a properly sized T&P relief valve." b. "A T&P valve shall be installed in a tapping directly in or on the tank, within 12 inches of the top of a vertical tank, or within six inches of the top of a horizontal tank, with no fittings between the valve and the tank, except that a bushing may be used ... or the valve shall be installed in the hot water outlet pipe as close to the top of the tank as possible but in no case more than five inches from the top of the tank." c. "The discharge outlet if [sic] the T&P relief valve shall be full-size and pipe using non-ferrous material or tubing rated to withstand the maximum relief valve temperature with no shut-off, to a fixture or a point to within twelve inches of the floor."

248 CMR 10.14(6)(f)1-2 (relief and T&P valves); 10.14(6)(c)1 (no check valve in cold supply); 10.14(6)(f)3 (vacuum relief) · confirm in the current 248 CMR

Why it exists

A water heater is a closed pressure vessel with a burner or element under it. If the thermostat or gas valve fails, the water keeps heating. Under pressure it can go past 212°F without boiling. If the tank then ruptures, that superheated water flashes to steam all at once, and steam takes up about 1,700 times the volume of the water (National Board). That is an explosion, not a leak. The T&P valve opens on either excessive pressure or excessive temperature. The valve's listed temperature setting, typically 210°F, holds the water below the atmospheric boiling point, so released water cannot flash into an explosion. Its pressure setting matches the tank's working pressure, generally 150 psi per A.O. Smith. These are listing and manufacturer values, not numbers written in 248 CMR. The discharge rules are about the person standing nearby. A full-size pipe with no shut-off, ending at a fixture or within 12 in. of the floor (248 CMR 10.14(6)(f)2.c), sends a sudden release of scalding water and steam at the floor instead of at someone's face, and lets it drain.

How it came to be

  1. 1982 — Spencer, Oklahoma: a water heater explodes into the Star Elementary School cafeteria, killing a teacher and six students. edweek.org
  2. 1982 — Investigators find the relief valve could not sense the tank temperature. edweek.org
  3. 1982 — UPI reports that the valves were mounted on pipe away from the heaters and failed to open. upi.com
  4. 1982 — CPSC warns of steam explosions in fireplace-powered water heaters without proper relief devices. cpsc.gov
  5. 1984 — National Board of Boiler and Pressure Vessel Inspectors on the physics. nationalboard.org

Make it stick

Spencer, Oklahoma, January 19, 1982, lunchtime. An 80-gallon water heater exploded into the Star Elementary School cafeteria, killing a teacher and six students. Initial findings reported that the relief valve's temperature probe was missing and that the valve had been improperly installed. A T&P valve only protects you if its probe can sense the hottest water.

On the exam

Expect MA location (within 12 in. of the top of a vertical tank, 6 in. for a horizontal tank, or in the hot outlet no more than 5 in. from the top; no fittings except a bushing), discharge rules (full size, non-ferrous or rated tubing, no shut-off, to a fixture or within 12 in. of the floor), relief rating not less than heater input (up to 200,000 BTU/h; ASME above that), and vacuum relief valves in the cold supply above the tank top. Also know that a check valve is prohibited in the cold-water supply to a water heater (10.14(6)(c)1), and that a closed system from a meter check or backflow device calls for a thermal expansion tank (10.14(3)(j)).

What people get wrong

Try it: 3 real practice questions

Q1. On a vertical storage water heater, a T&P relief valve installed in a tank tapping must be located within what distance of the top of the tank?

Q2. Which T&P relief valve discharge installation complies with 248 CMR?

Q3. Which of the following is prohibited in the cold-water supply to a hot water heater or storage tank?

These come from the PressureTest bank. Start 7 days free for the full bank, timed exam simulations and drawn isometric problems.

Teaching this? Present it in class · Assign it to your class

Sources

History is presented as history. The current Massachusetts rule is the box at the top — use it on the exam.