Massachusetts DFU Calculator: Size a Branch and a Stack

Add up drainage fixture units the way the exam expects, using the fixture values in 248 CMR 10.15 Table 1. The calculator then finds the smallest horizontal fixture branch (Table 2) and stack (Table 3) that can carry the load, and shows every step so you can check your own math.

Source: 248 CMR 10.15, Cornell Legal Information Institute (as amended effective 12/8/2023)

1. Pick your fixtures

How drain sizing by fixture units works

  1. Look up each fixture's DFU in Table 1 and multiply by how many there are.
  2. Add them up to get the total load on the pipe you're sizing.
  3. Go down the sizing table from the smallest pipe and stop at the first size whose maximum is at least your total.
  4. Check the water closet limit. A 3-inch horizontal branch and a 3-inch stack each carry not more than four water closets, no matter how few DFU you have. Five water closets means 4-inch.

That last step is the one people miss on the exam. Five tank-type water closets are only 20 DFU, well under the 34 DFU a 3-inch branch can take, but the water closet count still pushes you to 4-inch.

248 CMR 10.15 Table 1: drainage fixture units used in this calculator
FixtureDFU
Water closet, tank type4
Water closet, valve operated6
Lavatory1
Bathtub or tub & shower unit2
Shower stall, residential2
Kitchen sink, residential (with or without disposer)2
Laundry connection, residential3
Laundry/utility sink2
Drinking fountain / water station1
Floor/trench drain, 2-inch4
Floor/trench drain, 3-inch5
Floor/trench drain, 4-inch6
Urinal, wall lip4
Urinal, pedestal, siphon jet blowout6
Urinal, waterless1
Maximum DFU by pipe size (248 CMR 10.15 Table 2 and Table 3)
Pipe sizeHorizontal fixture branch (Table 2)Stack (Table 3)
1-1/2 in.34
2 in.68
3 in.34, not more than 4 water closets48, no more than 4 water closets
4 in.160240

This page covers pipe sizes through 4 inches. Larger sizes, building drains and sewers, and the per-branch-interval limits on stacks are in the full text of 248 CMR 10.15.

Keep studying

More free tools: trap arm length checker · individual vent size checker · all tools

Study aid — confirm with the current 248 CMR and your inspector. Values are from 248 CMR 10.15 as published by Cornell LII (amended effective 12/8/2023) and were checked in September 2026. This tool is not a design service and does not cover every rule that can affect a drain size. PressureTest is independent and not affiliated with the Commonwealth of Massachusetts, the Board of State Examiners of Plumbers & Gas Fitters or PSI.